INFRARED THERMOGRAPHY OF SUBSTATION EQUIPMENT IN HOT CLIMATES: A REVIEW OF ERROR SOURCES AND A FIELD PROTOCOL
The article reviews error sources of infrared inspection of substation equipment in hot climates. A radiometric model shows that default camera settings underestimate bare-metal temperatures by tens of degrees and compress phase-to-phase differences. A seven-step field protocol for surveys is proposed.
Сведения
- Опубликовано
- 2026 · Т. 4, № S/5, С. 26-38
- Язык
- Английский
- ISSN
- 3030-3702
- Издатель
- LLC Scienceproblems Team