ACCOUNTING OF POWER LOSSES FROM CORONA DISCHARGE WHEN SELECTING WIRES AND PHASE STRUCTURES OF MOUNTAIN POWER TRANSMISSION LINES WITH VOLTAGE OF 220–500 кV IN NATURAL AND CLIMATIC CONDITIONS OF KYRGYZSTAN
The choice of wire cross section and phase design for overhead power lines of 110 kV and above is largely determined by the corona restriction conditions. In the Kyrgyz power system, most of the 220–500 kV lines pass in difficult highlands characterized by extreme natural and climatic conditions, and therefore they have increased reliability requirements compared to lines passing in flat conditions. One of the components of losses in overhead power transmission lines is losses caused by corona discharge, which are especially noticeable on wires of mountain lines with a voltage of 220–500 kV, reaching several tens of kilowatts per kilometer of line, due to geophysical and climatic conditions of the highlands. The article provides an abbreviated framework version of the updated methodology for calculating the average annual power losses from the corona on mountain overhead power lines.